BMM503 Advanced feature contractor/service technician insulation tester and multimeter.
BMM503 Advanced feature contractor/service technician insulation tester and multimeter. Offers voltage ranges of 250, 500, and 1000 V.
BMM2000 With Milliamp and frequency.
BMM2500 Top of the range contractor/service technician insulation tester and multimeter featuring result storage, printing, and downloading. Offers the same voltage ranges as the BMM2000.
BMM80 High spec low voltage/specialty application insulation tester and multimeter. Features 50, 100, 250, 500, and 1000 V insulation ranges.
BMM2080 Advanced feature low voltage/specialty application insulation tester and multimeter. Like the BMM80, it offers voltage ranges of 50, 100, 250, 500, and 1000 V.
BMM2580 Top of the range low voltage/specialty application insulation tester and multimeter. Features include result storage, printing and downloading. Voltage ranges of 50, 100, 250, 500 and 1000 are also available in this model.
All instruments supplied with the SP1 Remote Switch Probe for hands-free operation.
Features
Patented analog and digital displays
Complete multimeter capability — Voltage measurement, Current, Frequency and Low-resistance measurement
mV transducer input
Selectable locking test button
Auto-Discharge Facility
3 Year Warranty
Live Circuit Warning
User selectable LCD backlight
Auto Shut Off
Test Result Storage
RS232 9 pin male D connector
Printer Output
Datalogging, storage and downloading
Waterproof and dustproof to IP54
SPECIFICATIONS
Insulation Measuring range
BD422115: 0.01 MΩ to 10 GΩ (Digital), 0 to 100 GΩ (Analog)
BD42270 and BD422112: 0.01 MΩ to 20 GΩ (Digital), 0 to 100 GΩ (Analog)
BD422114, BD422111, BD422113: 0.01 MΩ to 200 GΩ (Digital), 0 to 100 GΩ (Analog)
EN61577 operating range
0.10Ω to 99.9 Ω (0.10MΩ to 1,000 MΩ on BD422115 only)
Accuracy
±2% ±2 digits
Continuity Open circuit voltage
5 V ±1 V
Continuity Test current
210 mA ±10 mA (0 to 2Ω)
Continuity Zero offset at probe tips
0.10 Ω typical
Continuity Lead resistance zeroing
Up to 9.99 Ω
Resistance Measuring Range
0.01 kΩ to 9.99 MΩ (0 to 100 MΩ on analog scale with Auto Ranging or Range Lock Facility)
Resistance Accuracy
±3% ±2 digits
Resistance Open Circuit Voltage
5 V ±1 V
Resistance Short Circuit Current
25 μA ± 5 μA
Voltage Measuring range
±1 V to ±500 V (0 to 1000 V on analog scale)
Voltage Accuracy
0 to 500 V dc or ac (50/60 Hz) ±2% ±3 digits; 0 to 500 V 400 Hz ac ±5% ±3 digits
Millivolts Measuring Range
±0.1 mV to ±1999 mV (0 to 1000 mV on analog scale)
Millivolts Accuracy
10 mV to 1999 mV dc or ac (50/60 Hz) ±2% ±3 digit; 0.1 mV to 10 mV dc or ac (50/60 Hz) ±2% ±5 digits;
10 mV to 1999 mV ac (16 to 460 Hz) ±5% ±3 digits; 0.1 mV to 10 mV ac (16 to 460 Hz) ±5% ±5 digits
dc Millivolts Zeroing
Up to 9.9 mV
Capacitance Measuring Range (BD422114, BD422111, BD422113)